Menu 9 − User Functions 1

Mode: RFC‑A

Menu 9 provides the parameters for the following features:

  1. Logic functions
  2. Motorised Pot
  3. Binary Sum
  4. Timers

Logic functions

The logic functions are always active even if the sources and destinations are not routed to valid parameters. If the sources are not valid parameters then the source values are taken as 0. The update rate for each of the logic functions is always 4ms

The logic function consists of an AND gate with inverters on each input and an inverter on the output. Some of the other standard logic functions can be produced as shown in the table below.

Logic function Source 1 Invert Source 2 Invert Output Invert
AND 0 0 0
NAND 0 0 1
OR 1 1 1
NOR 1 1 0

A delay function is provided at the output of the logic functions. If Logic Function 1 Delay (09.009) or Logic Function 2 Delay (09.019) is positive then the output does not become 1 until the input to the delay has been at 1 for the delay time. If Logic Function 1 Delay (09.009) or Logic Function 2 Delay (09.019) is negative then the output remains at 1 until the input to the delay has been 0 for the delay time.


Motorised pot

If Motorised Pot Reset (09.028) = 1 then the motorised pot is disabled and held in its reset state with Motorised Pot Output (09.003) = 0.0%. If Motorised Pot Reset (09.028) = 0 the motorised pot is enabled even if Motorised Pot Destination (09.025) is not routed to a valid parameter. The sample rate of the motorised pot is always 4ms.

When the motorised pot is active Motorised Pot Output (09.003) can be increased or decreased by setting Motorised Pot Up (09.026) or Motorised Pot Down (09.027) to 1 respectively. If both Motorised Pot Up (09.026) and Motorised Pot Down (09.027) are 1 then Motorised Pot Output (09.003) is increased. The rate of change of Motorised Pot Output (09.003) is defined by Motorised Pot Rate (09.023) which gives the time to change from 0 to 100%. The time to change from -100% to 100% is Motorised Pot Rate (09.023) x 2. If Motorised Pot Bipolar Select (09.022) = 0 then Motorised Pot Output (09.003) is limited in the range 0.00% to 100.00%, otherwise it is allowed to change in the range from -100.00% to 100.00%.

Motorised Pot Mode (09.021) defines the mode of operation as given in the table below.

Motorised Pot Mode (09.021) Motorised Pot Output (09.003) Motorised Pot Up (09.026) and Motorised Pot Down (09.027) active
0 Reset to zero at power-up Always
1 Set to power-down value at power-up Always
2 Reset to zero at power-up When Drive Active (10.002) = 1
3 Set to power-down value at power-up When Drive Active (10.002) = 1
4 Reset to zero at power-up and when Drive Active (10.002) = 0 When Drive Active (10.002) = 1

Motorised Pot Scaling (09.024) introduces a scaling factor at the output of the motorised pot before the output is routed to the destination. If Motorised Pot Scaling (09.024) Motorised Pot Scaling (09.024) > 1.000 the output will exceed the range of the destination parameter, and so the destination parameter will be at its maximum or minimum before the output of the motorised pot reaches the limits of its range.


Binary sum

The binary sum function is always active even if the destination is not routed to valid a parameter. The update rate for the binary sum is always 4ms.

The output of the binary sum block is given by

Binary Sum Output (09.032) = Binary Sum Offset (09.034) + (Binary Sum Ones (09.029) x 1) + (Binary Sum Twos (09.030) x 2) + (Binary Sum Fours (09.031) x 4)

Binary Sum Destination (09.033) defines the destination for the binary sum output. The routing for this destination is special if the maximum of the destination parameter ≤ 7 + [Binary Sum Offset (09.034)] as follows:

Destination parameter = Binary Sum Output (09.032), subject to the parameter minimum

Otherwise Binary Sum Output (09.032) is routed in the same way as any other destination where the destination target is at its full scale value when the Binary Sum Output (09.032) = 7 + Offset.


Timers

If the enable input to a timer is active and the repeat function is set to a non-zero value then the timer is active even if the destination is not routed to valid a parameter. The timers are updated in the background task and have a resolution of 1s.

The following is a description of Timer 1, but Timer 2 behaves in the same way. If Timer 1 Invert = 0 then Timer 1 Output (09.042) is inactive before the Timer 1 Start Date (09.035) / Timer 1 Start Time (09.036), active between this date/time and Timer 1 Stop Date (09.037) / Timer 1 Stop Time (09.038) and then inactive after the stop time/date within the timer 1 repeat period as shown in the diagram below.

Timer 1 Repeat Function (09.039) defines the length of the repeat period. For example if Timer 1 Repeat Function (09.039) = 2 then the repeat period is one day. The output is inactive until the time reaches the hour, minute and second defined in Timer 1 Start Time (09.036), and remains active until the time reaches the hour, minute and second defined in Timer 1 Stop Time (09.038). Different repeat periods may be selected as given in the table below. The table shows the constituent parts of the date and time that are used to determine the start and stop events. If the repeat period is set to every week then Timer 1 Start Date (09.035) and Timer 1 Stop Date (09.037) define the day of the week and not the date (i.e. 00.00.00 = Sunday, 00.00.01 = Monday, etc.). If the stop time event is set to occur at or before the start time event or the Timer 1 Repeat Function (09.039) = 0 or Timer 1 Enable (09.040) = 0 the output remains inactive at all times (i.e. Timer 1 Output (09.042) = 0 if Timer 1 Invert = 0).

Timer 1 Repeat Function (09.039) Repeat period Second Minute Hour Day Month Year Day of week
0 None






1 Hour






2 Day





3 Week

 

 

 

4 Month




5 Year



6 One off


7 Minute







As Timer 1 Invert inverts the timer output it can be used to give an active state of 0 instead of 1. Alternatively it can be used to give an active state of 1, but for a time period that spans the ends of the repeat period as shown in the example above. It should be noted that if this method is used to allow the active period to span the ends of the repeat period then if the timer is disabled the output of the timer block before the invert becomes 0, and so the final output of the timer after the invert is 1.

If Date/Time Selector  (06.019) is changed and the drive is reset then the source for the timers will change, therefore Timer 1 Repeat Function (09.039) and Timer 2 Repeat Function (09.049) are reset to 0 to disable the timers and the date and time entries in the trip log are cleared.


Parameter09.001  Logic Function 1 Output
Short descriptionShows the output state of logic function 1
ModeRFC‑A
Minimum0Maximum1
Default Units 
Type1 Bit VolatileUpdate Rate4ms write
Display FormatStandardDecimal Places0
CodingRO, ND, NC, PT

Logic Function 1 Output (09.001) shows the output of logic function 1.


Parameter09.002  Logic Function 2 Output
Short descriptionShows the output state of logic function 2
ModeRFC‑A
Minimum0Maximum1
Default Units 
Type1 Bit VolatileUpdate Rate4ms write
Display FormatStandardDecimal Places0
CodingRO, ND, NC, PT

Logic Function 2 Output (09.002) shows the output of logic function 2.


Parameter09.003  Motorised Pot Output
Short descriptionShows the output level of the motorised pot function
ModeRFC‑A
Minimum-100.00Maximum100.00
Default Units%
Type16 Bit Power Down SaveUpdate Rate4ms write
Display FormatStandardDecimal Places2
CodingRO, ND, NC, PT

Motorised Pot Output (09.003) shows the output of the motorised pot function.


Parameter09.004  Logic Function 1 Source 1
Short descriptionDefines input source 1 of logic function 1
ModeRFC‑A
Minimum0.000Maximum30.999
Default0.000Units 
Type16 Bit User SaveUpdate RateDrive reset read
Display FormatStandardDecimal Places3
CodingRW, PT, BU

Logic Function 1 Source 1 (09.004) defines input souce 1 of logic function 1.


Parameter09.005  Logic Function 1 Source 1 Invert
Short descriptionSet to invert input 1 of logic function 1
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type1 Bit User SaveUpdate Rate4ms read
Display FormatStandardDecimal Places0
CodingRW

Setting Logic Function 1 Source 1 Invert (09.005) inverts input 1 of logic function 1.


Parameter09.006  Logic Function 1 Source 2
Short descriptionDefines input source 2 of logic function 1
ModeRFC‑A
Minimum0.000Maximum30.999
Default0.000Units 
Type16 Bit User SaveUpdate RateDrive reset read
Display FormatStandardDecimal Places3
CodingRW, PT, BU

Logic Function 1 Source 2 (09.006) defines input source 2 of logic function 1.


Parameter09.007  Logic Function 1 Source 2 Invert
Short descriptionSet to invert input 2 of logic function 1
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type1 Bit User SaveUpdate Rate4ms read
Display FormatStandardDecimal Places0
CodingRW

Setting Logic Function 1 Source 2 Invert (09.007) inverts input 2 of logic function 1.


Parameter09.008  Logic Function 1 Output Invert
Short descriptionSet to invert the ouptut of logic function 1
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type1 Bit User SaveUpdate Rate4ms read
Display FormatStandardDecimal Places0
CodingRW

Setting Logic Function 1 Output Invert (09.008) inverts the output of logic function 1.


Parameter09.009  Logic Function 1 Delay
Short descriptionDefines the output delay of logic function 1
ModeRFC‑A
Minimum-25.0Maximum25.0
Default0.0Unitss
Type16 Bit User SaveUpdate Rate4ms read
Display FormatStandardDecimal Places1
CodingRW

Logic Function 1 Delay (09.009) defines the delay at the output of logic function 1. If Logic Function 1 Delay (09.009) is positive then the output does not become 1 until the input to the delay has been at 1 for the delay time. If Logic Function 1 Delay (09.009) is negative then the output remains at 1 until the input to the delay has been 0 for the delay time.


Parameter09.010  Logic Function 1 Destination
Short descriptionDefines the output destination of logic function 1
ModeRFC‑A
Minimum0.000Maximum30.999
Default0.000Units 
Type16 Bit User SaveUpdate RateDrive reset read
Display FormatStandardDecimal Places3
CodingRW, DE, PT, BU

Logic Function 1 Destination (09.010) defines the output destination of logic function 1.


Parameter09.014  Logic Function 2 Source 1
Short descriptionDefines input source 1 of logic function 2
ModeRFC‑A
Minimum0.000Maximum30.999
Default0.000Units 
Type16 Bit User SaveUpdate RateDrive reset read
Display FormatStandardDecimal Places3
CodingRW, PT, BU

Logic Function 2 Source 1 (09.014) defines input source 1 of logic function 2.


Parameter09.015  Logic Function 2 Source 1 Invert
Short descriptionSet to invert input 1 of logic function 2
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type1 Bit User SaveUpdate Rate4ms read
Display FormatStandardDecimal Places0
CodingRW

Setting Logic Function 2 Source 1 Invert (09.015) inverts input 1 of logic function 2.


Parameter09.016  Logic Function 2 Source 2
Short descriptionDefines input source 2 of logic function 2
ModeRFC‑A
Minimum0.000Maximum30.999
Default0.000Units 
Type16 Bit User SaveUpdate RateDrive reset read
Display FormatStandardDecimal Places3
CodingRW, PT, BU

Logic Function 2 Source 2 (09.016) defines input source 2 of logic function 2.


Parameter09.017  Logic Function 2 Source 2 Invert
Short descriptionSet to invert input 2 of logic function 2
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type1 Bit User SaveUpdate Rate4ms read
Display FormatStandardDecimal Places0
CodingRW

Setting Logic Function 2 Source 2 Invert (09.017) inverts input 2 of logic function 2.


Parameter09.018  Logic Function 2 Output Invert
Short descriptionSet to invert the ouptut of logic function 2
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type1 Bit User SaveUpdate Rate4ms read
Display FormatStandardDecimal Places0
CodingRW

Setting Logic Function 2 Output Invert (09.018) inverts the output of logic function 2.


Parameter09.019  Logic Function 2 Delay
Short descriptionDefines the output delay of logic function 2
ModeRFC‑A
Minimum-25.0Maximum25.0
Default0.0Unitss
Type16 Bit User SaveUpdate Rate4ms read
Display FormatStandardDecimal Places1
CodingRW

Logic Function 2 Delay (09.019) defines the delay at the output of logic function 1. If Logic Function 2 Delay (09.019) is positive then the output does not become 1 until the input to the delay has been at 1 for the delay time. If Logic Function 2 Delay (09.019) is negative then the output remains at 1 until the input to the delay has been 0 for the delay time.


Parameter09.020  Logic Function 2 Destination
Short descriptionDefines the output destination of logic function 2
ModeRFC‑A
Minimum0.000Maximum30.999
Default0.000Units 
Type16 Bit User SaveUpdate RateDrive reset read
Display FormatStandardDecimal Places3
CodingRW, DE, PT, BU

Logic Function 2 Destination (09.020) defines the output destination of logic function 2.


Parameter09.021  Motorised Pot Mode
Short descriptionDefines the motorised pot mode
ModeRFC‑A
Minimum0Maximum4
Default0Units 
Type8 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places0
CodingRW

Motorised Pot Mode (09.021) defines the mode of operation as given in the table below.

Motorised Pot Mode (09.021) Motorised Pot Output (09.003) Motorised Pot Up (09.026) and Motorised Pot Down (09.027) active
0 Reset to zero at power-up Always
1 Set to power-down value at power-up Always
2 Reset to zero at power-up When Drive Active (10.002) = 1
3 Set to power-down value at power-up When Drive Active (10.002) = 1
4 Reset to zero at power-up and when Drive Active (10.002) = 0 When Drive Active (10.002) = 1


Parameter09.022  Motorised Pot Bipolar Select
Short descriptionSet to enable bipolar operation of the motorised pot
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type1 Bit User SaveUpdate Rate4ms read
Display FormatStandardDecimal Places0
CodingRW

If Motorised Pot Bipolar Select (09.022) = 0 then Motorised Pot Output (09.003) is limited in the range 0.00% to 100.00%, otherwise it is allowed to change in the range from -100.00% to 100.00%.


Parameter09.023  Motorised Pot Rate
Short descriptionDefines the rate of change of the motorised pot output
ModeRFC‑A
Minimum0Maximum250
Default20Unitss
Type8 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, BU

The rate of change of Motorised Pot Output (09.003) is defined by Motorised Pot Rate (09.023) which gives the time to change from 0 to 100%. The time to change from -100% to 100% is Motorised Pot Rate (09.023) x 2.


Parameter09.024  Motorised Pot Scaling
Short descriptionDefines the scaling applied to the motorised pot output
ModeRFC‑A
Minimum0.000Maximum4.000
Default1.000Units 
Type16 Bit User SaveUpdate Rate4ms read
Display FormatStandardDecimal Places3
CodingRW

Motorised Pot Scaling (09.024) introduces a scaling factor at the output of the motorised pot before the output is routed to the destination. If Motorised Pot Scaling (09.024) > 1.000 the output will exceed the range of the destination parameter, and so the destination parameter will be at its maximum or minimum before the output of the motorised pot reaches the limits of its range.


Parameter09.025  Motorised Pot Destination
Short descriptionDefines the output destination of the motorised pot
ModeRFC‑A
Minimum0.000Maximum30.999
Default0.000Units 
Type16 Bit User SaveUpdate RateDrive reset read
Display FormatStandardDecimal Places3
CodingRW, DE, PT, BU

Motorised Pot Destination (09.025) defines the output destination of the motorised pot function.


Parameter09.026  Motorised Pot Up
Short descriptionSet to increase the motorised pot output
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type1 Bit VolatileUpdate Rate4ms read
Display FormatStandardDecimal Places0
CodingRW, NC

If Motorised Pot Up (09.026) = 1, then the Motorised Pot Output (09.003) will increase.


Parameter09.027  Motorised Pot Down
Short descriptionSet to decrese the motorised pot output
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type1 Bit VolatileUpdate Rate4ms read
Display FormatStandardDecimal Places0
CodingRW, NC

If Motorised Pot Down (09.027) = 1 and Motorised Pot Up (09.026) = 0 , then the Motorised Pot Output (09.003) will decrease.


Parameter09.028  Motorised Pot Reset
Short descriptionSet to reset the motorised pot output to zero
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type1 Bit VolatileUpdate Rate4ms read
Display FormatStandardDecimal Places0
CodingRW, NC

If Motorised Pot Reset (09.028) = 1 then the motorised pot is disabled and held in its reset state with Motorised Pot Output (09.003) = 0.0%. If Motorised Pot Reset (09.028) the motorised pot is enabled even if Motorised Pot Destination (09.025) is not routed to a valid parameter.


Parameter09.029  Binary Sum Ones
Short descriptionSet to add one to the binary sum output
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type1 Bit VolatileUpdate Rate4ms read
Display FormatStandardDecimal Places0
CodingRW

See Binary Sum Output (09.032).


Parameter09.030  Binary Sum Twos
Short descriptionSet to add two to the binary sum output
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type1 Bit VolatileUpdate Rate4ms read
Display FormatStandardDecimal Places0
CodingRW

See Binary Sum Output (09.032).


Parameter09.031  Binary Sum Fours
Short descriptionSet to add three to the binary sum output
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type1 Bit VolatileUpdate Rate4ms read
Display FormatStandardDecimal Places0
CodingRW

See Binary Sum Output (09.032).


Parameter09.032  Binary Sum Output
Short descriptionShows the output level of the binary sum
ModeRFC‑A
Minimum0Maximum255
Default Units 
Type8 Bit VolatileUpdate Rate4ms write
Display FormatStandardDecimal Places0
CodingRO, ND, NC, PT, BU

The binary sum function is always active even if the destination is not routed to valid a parameter. The update rate for the binary sum is always 4ms.

The output of the binary sum block is given by

Binary Sum Output (09.032) = Binary Sum Offset (09.034) + (Binary Sum Ones (09.029) x 1) + (Binary Sum Twos (09.030) x 2) + (Binary Sum Fours (09.031) x 4)

Binary Sum Destination (09.033) defines the destination for the binary sum output. The routing for this destination is special if the maximum of the destination parameter ≤ 7 + [Binary Sum Offset (09.034)] as follows:

Destination parameter = Binary Sum Output (09.032), subject to the parameter minimum

Otherwise Binary Sum Output (09.032) is routed in the same way as any other destination where the destination target is at its full scale value when the Binary Sum Output (09.032) = 7 + Binary Sum Offset (09.034)

Example:

09.033 = 01.015

09.029 = 0

09.030 = 1

09.031 = 0

09.034 = 0

So 09.032 = 2

And 01.015 = (01.015[MAX] x 09.032)  / (7 + 09.034)

01.015 = (9 x 2)/(7+0) = 2.57 = 3 (rounded to nearest integer)

If 09.034 = 1 then 01.015 = (9 x 3)/(7+1) = 3.37 = 3 (rounded to nearest integer)

If 09.034 = 2 then 01.015 = (9 x 4)/(7+2) = 4


Parameter09.033  Binary Sum Destination
Short descriptionDefines the output destination of the binary sum
ModeRFC‑A
Minimum0.000Maximum30.999
Default0.000Units 
Type16 Bit User SaveUpdate RateDrive reset read
Display FormatStandardDecimal Places3
CodingRW, DE, PT, BU

Binary Sum Destination (09.033) defines the destination for the binary sum output.

See Binary Sum Output (09.032) for more information.


Parameter09.034  Binary Sum Offset
Short descriptionDefines the offset added to the output of the binary sum
ModeRFC‑A
Minimum0Maximum248
Default0Units 
Type8 Bit User SaveUpdate Rate4ms read
Display FormatStandardDecimal Places0
CodingRW, BU

See Binary Sum Output (09.032).


Parameter09.035  Timer 1 Start Date
Short descriptionDefines the start date for timer 1
ModeRFC‑A
Minimum0
(Display: 00-00-00)
Maximum311299
(Display: 31-12-99)
Default0
(Display: 00-00-00)
Units 
Type32 Bit User SaveUpdate RateBackground read
Display FormatDateDecimal Places0
CodingRW

Timer 1 Start Date (09.035) defines the start date within the repeat period of timer 1.

See Timer 1 Repeat Function (09.039) for more information.


Parameter09.036  Timer 1 Start Time
Short descriptionDefines the start time for timer 1
ModeRFC‑A
Minimum0
(Display: 00:00:00)
Maximum235959
(Display: 23:59:59)
Default0
(Display: 00:00:00)
Units 
Type32 Bit User SaveUpdate RateBackground read
Display FormatTimeDecimal Places0
CodingRW

Timer 1 Start Time (09.036) defines the start time within the repeat period of timer 1.

See Timer 1 Repeat Function (09.039) for more information.


Parameter09.037  Timer 1 Stop Date
Short descriptionDefines the stop date for timer 1
ModeRFC‑A
Minimum0
(Display: 00-00-00)
Maximum311299
(Display: 31-12-99)
Default0
(Display: 00-00-00)
Units 
Type32 Bit User SaveUpdate RateBackground read
Display FormatDateDecimal Places0
CodingRW

Timer 1 Stop Date (09.037) defines the stop date within the repeat period of timer 1.

See Timer 1 Repeat Function (09.039) for more information.


Parameter09.038  Timer 1 Stop Time
Short descriptionDefines the stop time for timer 1
ModeRFC‑A
Minimum0
(Display: 00:00:00)
Maximum235959
(Display: 23:59:59)
Default0
(Display: 00:00:00)
Units 
Type32 Bit User SaveUpdate RateBackground read
Display FormatTimeDecimal Places0
CodingRW

Timer 1 Stop Time (09.038) defines the stop time within the repeat period of timer 1.

See Timer 1 Repeat Function (09.039) for more information.


Parameter09.039  Timer 1 Repeat Function
Short descriptionDefines the length of the repeat period
ModeRFC‑A
Minimum0Maximum7
Default0Units 
Type8 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places0
CodingRW, TE

ValueText
0None
11
22
33
44
55
66
77

Timer 1 Repeat Function (09.039) defines the length of the repeat period. For example if Timer 1 Repeat Function (09.039) = 2 then the repeat period is one day. The output is inactive until the time reaches the hour, minute and second defined in Timer 1 Start Time (09.036), and remains active until the time reaches the hour, minute and second defined in Timer 1 Stop Time (09.038). Different repeat periods may be selected as given in the table below. The table shows the constituent parts of the date and time that are used to determine the start and stop events. If the repeat period is set to every week then Timer 1 Start Date (09.035) and Timer 1 Stop Date (09.037) define the day of the week and not the date (i.e. 00.00.00 = Sunday, 00.00.01 = Monday, etc.). If the stop time event is set to occur at or before the start time event or the Timer 1 Repeat Function (09.039) = 0 or Timer 1 Enable (09.040) = 0 the output remains inactive at all times (i.e. Timer 1 Output (09.042) = 0 if Timer 1 Invert = 0).

Timer 1 Repeat Function (09.039) Repeat period Second Minute Hour Day Month Year Day of week
0 None






1 Hour






2 Day





3 Week




4 Month




5 Year



6 One off


7 Minute








Parameter09.040  Timer 1 Enable
Short descriptionSet to enable the timer 1 function
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type1 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places0
CodingRW

Timer 1 Enable (09.040) enables the timer 1 function. If Timer 1 Enable (09.040) = 0, then the output of the timer is always inactive, i.e. Timer 1 Output (09.042) =0.


Parameter09.041  Timer 1 Invert
Short descriptionSet to invert the output of timer 1
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type1 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places0
CodingRW

Timer 1 Invert (09.041) inverts the timer output to give an active state of 0 instead of 1. Alternatively it can be used to give an active state of 1, but for a time period that spans the ends of the repeat period as shown in the example above. It should be noted that if this method is used to allow the active period to span the ends of the repeat period then if the timer is disabled the output of the timer block before the invert becomes 0, and so the final output of the timer after the invert is 1.

See  User Functions 1  for more information.


Parameter09.042  Timer 1 Output
Short descriptionShows the output state of timer function 1
ModeRFC‑A
Minimum0Maximum1
Default Units 
Type1 Bit VolatileUpdate RateBackground write
Display FormatStandardDecimal Places0
CodingRO, ND, NC, PT

Timer 1 Output (09.042) shows the output of the timer function 1.


Parameter09.043  Timer 1 Destination
Short descriptionDefines the output destination of timer function 1
ModeRFC‑A
Minimum0.000Maximum30.999
Default0.000Units 
Type16 Bit User SaveUpdate RateDrive reset read
Display FormatStandardDecimal Places3
CodingRW, DE, PT, BU

Timer 1 Destination (09.043) defines the output destination of timer function 1.


Parameter09.045  Timer 2 Start Date
Short descriptionDefines the start date for timer 2
ModeRFC‑A
Minimum0
(Display: 00-00-00)
Maximum311299
(Display: 31-12-99)
Default0
(Display: 00-00-00)
Units 
Type32 Bit User SaveUpdate RateBackground read
Display FormatDateDecimal Places0
CodingRW

Timer 2 Start Date (09.045) defines the start date within the repeat period of timer 2.

See Timer 1 Repeat Function (09.039) for more information.


Parameter09.046  Timer 2 Start Time
Short descriptionDefines the start time for timer 2
ModeRFC‑A
Minimum0
(Display: 00:00:00)
Maximum235959
(Display: 23:59:59)
Default0
(Display: 00:00:00)
Units 
Type32 Bit User SaveUpdate RateBackground read
Display FormatTimeDecimal Places0
CodingRW

Timer 2 Start Time (09.046) defines the start time within the repeat period of timer 2.

See Timer 1 Repeat Function (09.039) for more information.


Parameter09.047  Timer 2 Stop Date
Short description 
ModeRFC‑A
Minimum0
(Display: 00-00-00)
Maximum311299
(Display: 31-12-99)
Default0
(Display: 00-00-00)
Units 
Type32 Bit User SaveUpdate RateBackground read
Display FormatDateDecimal Places0
CodingRW

Timer 2 Stop Date (09.047) defines the stop date within the repeat period of timer 2.

See Timer 1 Repeat Function (09.039) for more information.


Parameter09.048  Timer 2 Stop Time
Short descriptionDefines the stop time for timer 2
ModeRFC‑A
Minimum0
(Display: 00:00:00)
Maximum235959
(Display: 23:59:59)
Default0
(Display: 00:00:00)
Units 
Type32 Bit User SaveUpdate RateBackground read
Display FormatTimeDecimal Places0
CodingRW

Timer 2 Stop Time (09.048) defines the stop time within the repeat period of timer 2.

See Timer 1 Repeat Function (09.039) for more information.


Parameter09.049  Timer 2 Repeat Function
Short descriptionDefines the length of the repeat period
ModeRFC‑A
Minimum0Maximum7
Default0Units 
Type8 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places0
CodingRW, TE

ValueText
0None
11
22
33
44
55
66
77

See Timer 1 Repeat Function (09.039).


Parameter09.050  Timer 2 Enable
Short descriptionSet to enable the timer 2 function
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type1 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places0
CodingRW

Timer 2 Enable (09.050) enables the timer 2 function. If Timer 2 Enable (09.050) = 0, then the output of the timer is always inactive, i.e. Timer 2 Output (09.052) = 0.


Parameter09.051  Timer 2 Invert
Short descriptionSet to invert the output of timer 2
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type1 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places0
CodingRW

Timer 2 Invert (09.051) inverts the timer output to give an active state of 0 instead of 1.

See Timer 1 Invert (09.041) for more information.


Parameter09.052  Timer 2 Output
Short descriptionShows the output state of timer function 2
ModeRFC‑A
Minimum0Maximum1
Default Units 
Type1 Bit VolatileUpdate RateBackground write
Display FormatStandardDecimal Places0
CodingRO, ND, NC, PT

Timer 2 Output (09.052) shows the output of timer function 2.


Parameter09.053  Timer 2 Destination
Short descriptionDefines the output destination of timer function 2
ModeRFC‑A
Minimum0.000Maximum30.999
Default0.000Units 
Type16 Bit User SaveUpdate RateDrive reset read
Display FormatStandardDecimal Places3
CodingRW, DE, PT, BU

Timer 2 Destination (09.053) defines the output destination of timer function 2.