Menu 7 − Analog I/O

Mode: Open‑Loop

 

 


Parameter07.001  Analog Input 1
Short descriptionDisplays the value of analog input 1
ModeOpen‑Loop
Minimum-100.00Maximum100.00
Default Units%
Type16 Bit VolatileUpdate Rate4ms
Display FormatStandardDecimal Places2
CodingRO, FI, ND, NC, PT

The Analog input 1 can operate in different modes as defined by Analog Input 1 Mode (07.007) including current modes. See Analog I/O.

Voltage mode: Resolution of 11 bits. It is a single ended unipolar voltage input 0V-10V

Current mode: Resolution of 11 bits. It is a single ended unipolar 0-20mA

The "Input Level" is defined for the different modes in the table below.

Mode Input Level
Voltage (Input Voltage/ 10V) x 100.00%
0-20mA (Input Current / 20mA) x 100.00%
20-0mA (20mA - Input Current) / 20mA x 100.00%
4-20mA (Input Current - 4mA) / 16mA x 100.00%
20-4mA

(20mA - Input Current) / 16mA x 100.00%


Parameter07.002  Analog Input 2
Short descriptionDisplays the value of analog input 2
ModeOpen‑Loop
Minimum-100.00Maximum100.00
Default Units%
Type16 Bit VolatileUpdate Rate4ms
Display FormatStandardDecimal Places2
CodingRO, FI, ND, NC, PT

 See Analog I/O.

Voltage mode: This input is a unipolar voltage 0-10V.

Digital mode: This input can also be configured as a digital input in which case this parameter will indicate 0.00% or 100.00% depending on the state of the input.

The "Input Level" is defined for the different modes in the table below.

Mode Input Level
Voltage (Input Voltage/ 10V) x 100.00%
Digital 0.00% (corresponds to logical 0 if less than 9V) or 100.0% (corresponds to logical 1 if more than 11V)


Parameter07.004  Stack Temperature
Short descriptionDisplays the temperature currently being measured on the heat sink
ModeOpen‑Loop
Minimum-250Maximum250
Default Units°C
Type16 Bit VolatileUpdate RateBackground write
Display FormatStandardDecimal Places0
CodingRO, ND, NC, PT

This parameter displays the temperature currently being measured on the heat sink. This is used as part of the drive thermal model, see Drive Over-temperature Alarm (10.018) for further details.


Parameter07.005  Auxiliary Temperature
Short descriptionDisplays the temperature currently being measured on the power system
ModeOpen‑Loop
Minimum-250Maximum250
Default Units°C
Type16 Bit VolatileUpdate RateBackground write
Display FormatStandardDecimal Places0
CodingRO, ND, NC, PT

This parameter displays the temperature currently being measured on the power system on large frames. This is used as part of the drive thermal model.


Parameter07.007  Analog Input 1 Mode
Short descriptionDefines the mode of analog input 1
ModeOpen‑Loop
Minimum-6Maximum6
Default6Units 
Type8 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places0
CodingRW, TE

ValueText
-64-20.S
-520-4.S
-44-20.L
-320-4.L
-24-20.H
-120-4.H
00-20
120-0
24-20.tr
320-4.tr
44-20
520-4
6Volt

See Analog Input 1 (07.001).

The table below gives all the possible analog input modes.

In 4-20mA and 20-4mA current input modes the software detects a current input less than 3mA as a current loop loss and initiates an action depending on the mode set in the table below.

Value Mode Function

-6

4-20mA Stop 4-20mA with stop on current loop loss
-5 20-4mA Stop 20-4mA with stop on current loop loss
-4 4-20mA Low 4-20mA with switching to a low speed set in Analog Input 1 Preset on Current Loss (07.026) on current loop loss
-3 20-4mA Low 20-4mA with switching to a low speed set in Analog Input 1 Preset on Current Loss (07.026) on current loop loss
-2 4-20mA Hold 4-20mA with hold at level before loss on current loop loss (1)
-1 20-4mA Hold 20-4mA with hold at level before loss on current loop loss (1)
0 0-20mA 0-20mA
1 20-0mA 20-0mA
2 4-20mA Trip 4-20mA with An Input 1 Loss trip on current loss.
3 20-4mA Trip 20-4mA with An Input 1 Loss trip on current loss.
4 4-20mA 4-20mA with no action on current loop loss (input taken as 0%).
5 20-4mA 20-4mA with no action on current loop loss (input taken as 0%).
6 Voltage Voltage input

(1) Analog input level remains at the value it had in the previous sample before the current fell below 3mA.


Parameter07.008  Analog Input 1 Scaling
Short descriptionDefines the scaling factor of analog input 1
ModeOpen‑Loop
Minimum0.000Maximum10.000
Default1.000Units 
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places3
CodingRW

See Analog I/O.

Analog Input 1 (07.001) is modified by Analog Input 1 Scaling (07.008), Analog Input 1 Offset (07.030) and Analog Input 1 Invert (07.009) before it is routed to its destination as follows:

A1O = Analog Input 1 (07.001) + Analog Input 1 Offset (07.030)
A1O is the value after the offset has been applied and is limited between -100.00% and 100.00%

A1S = A1O x Analog Input 1 Scaling (07.008)
A1S is the value after the scaling and the offset have been applied and is limited between -100.00% and 100.00%

If Analog Input 1 Invert (07.009) = 0 then A1I = A1S otherwise A1I = -A1S

A1I is the value after the invert, scaling and offset have been applied and is the final value that is routed to the destination defined by


Parameter07.009  Analog Input 1 Invert
Short descriptionInverts the signal for analog input 1
ModeOpen‑Loop
Minimum0Maximum1
Default0Units 
Type1 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places0
CodingRW

See Analog Input 1 Scaling (07.008).


Parameter07.010  Analog Input 1 Destination A
Short descriptionDefines the output parameter for analog input 1
ModeOpen‑Loop
Minimum0.000Maximum30.999
Default1.036Units 
Type16 Bit User SaveUpdate RateDrive reset read
Display FormatStandardDecimal Places3
CodingRW, DE, PT

See Analog Input 1 Scaling (07.008).


Parameter07.011  Analog Input 2 Mode
Short descriptionDefines the mode for analog input 2
ModeOpen‑Loop
Minimum6Maximum7
Default6Units 
Type8 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places0
CodingRW, TE

ValueText
6Volt
7dig

See Analog Input 2 (07.002).

The table below gives all the possible analogue input modes.

Value Mode Function
6 Voltage Voltage
7 Digital Digital


Parameter07.012  Analog Input 2 Scaling
Short descriptionDefines the scaling factor for analog input 2
ModeOpen‑Loop
Minimum0.000Maximum10.000
Default1.000Units 
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places3
CodingRW

See Analog I/O.

Analog Input 2 (07.002) is modified by Analog Input 2 Scaling (07.012)Analog Input 2 Offset (07.031) and Analog Input 2 Invert (07.013) before it is routed to its destination as follows:

A2O = Analog Input 2 (07.002)+ Analog Input 2 Offset (07.031)
A2O is the value after the offset has been applied and is limited between 0.00% and 100.00%

A2S = A2O x Analog Input 2 Scaling (07.012)
A2S is the value after the scaling and the offset have been applied and is limited between 0.00% and 100.00%

If Analog Input 2 Invert (07.013) = 0 then A2I = A2S otherwise A2I = -A2S

A2I is the value after the invert, scaling and offset have been applied and is the final value that is routed to the destination defined by


Parameter07.013  Analog Input 2 Invert
Short descriptionInverts the signal for analog input 2
ModeOpen‑Loop
Minimum0Maximum1
Default0Units 
Type1 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places0
CodingRW

See Analog Input 2 Scaling (07.012).


Parameter07.014  Analog Input 2 Destination A
Short descriptionDefines the output parameter for analog input 2
ModeOpen‑Loop
Minimum0.000Maximum30.999
Default1.037Units 
Type16 Bit User SaveUpdate RateDrive reset read
Display FormatStandardDecimal Places3
CodingRW, DE, PT

See Analog Input 2 Scaling (07.012).


Parameter07.019  Analog Output 1 Source A
Short descriptionDefines the input parameter for analog output 1
ModeOpen‑Loop
Minimum0.000Maximum30.999
Default2.001Units 
Type16 Bit User SaveUpdate RateDrive reset read
Display FormatStandardDecimal Places3
CodingRW, PT

Analog Output 1 Source A (07.019) defines the source parameter for Analog Output 1. The modulus of the value of the source parameter is then scaled with Analog Output 1 Scaling (07.020) and if the scaling is greater than 1.000 the value is clamped to 100.0% which corresponds to 10V on the output.


Parameter07.020  Analog Output 1 Scaling
Short descriptionDefines the scaling factor for analog output 1
ModeOpen‑Loop
Minimum0.000Maximum40.000
Default1.000Units 
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places3
CodingRW, BU

See Analog Output 1 Source A (07.019).

An automatic scaling takes place when parameters are selected for an analog output. The maximum value of the parameter is used as the full scale value such that the analog output will be at full scale when the parameter value is at its maximum value. Some parameters do not reach their maximum values and so this parameter is provided for the user to apply further scaling and configure a bigger range of the analog output to be used.


Parameter07.026  Analog Input 1 Preset on Current Loss
Short descriptionDefines the current level held on analog input 1 current loss
ModeOpen‑Loop
Minimum4.00Maximum20.00
Default4.00UnitsmA
Type16 Bit User SaveUpdate Rate4ms read
Display FormatStandardDecimal Places2
CodingRW

If Analog Input 1 Mode (07.007) is set to the 4-20mA Low or 20-4mA Low modes and the current falls below 3mA (Analog Input 1 Current Loop Loss (07.028) = 1) then the analog input 1 is held to Analog Input 1 Preset on Current Loss (07.026).

If the current rise above 4mA (Analog Input 1 Current Loop Loss (07.028) = 0) then the analog input 1 current is used as normal.


Parameter07.028  Analog Input 1 Current Loop Loss
Short descriptionDisplays when analog input 1 falls below 3mA
ModeOpen‑Loop
Minimum0Maximum1
Default Units 
Type1 Bit VolatileUpdate RateBackground write
Display FormatStandardDecimal Places0
CodingRO, ND, NC, PT

See Analog Input 1 Preset on Current Loss (07.026).


Parameter07.030  Analog Input 1 Offset
Short descriptionDefines the offset of analog input 1
ModeOpen‑Loop
Minimum-100.00Maximum100.00
Default0.00Units%
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places2
CodingRW

See Analog Input 1 Scaling (07.008).


Parameter07.031  Analog Input 2 Offset
Short descriptionDefines the offset of analog input 2
ModeOpen‑Loop
Minimum-100.00Maximum100.00
Default0.00Units%
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places2
CodingRW

See Analog Input 2 Scaling (07.012).


Parameter07.034  Inverter Temperature
Short descriptionDisplays the estimated junction temperature of the hottest power device within the drive inverter
ModeOpen‑Loop
Minimum-250Maximum250
Default Units°C
Type16 Bit VolatileUpdate RateBackground write
Display FormatStandardDecimal Places0
CodingRO, ND, NC, PT

Inverter Temperature (07.034) shows the estimated junction temperature of the hottest power device within the drive inverter. If this temperature exceeds the switch down threshold defined for the power stage the switching frequency is reduced provided this feature has not been disabled (i.e. Auto-switching Frequency Change Disable (05.035) = 0) or the minimum switching frequency has not been reached. The switching frequency can be reduced from 12kHz to 6kHz to 3kHz, or from 16kHz to 8kHz to 4kHz to 2kHz. If the switching frequency has been reduced the drive will attempt to restore it to the required level when the Inverter Temperature (07.034) reduces.


Parameter07.035  Percentage Of d.c. Link Thermal Trip Level
Short descriptionDisplays the percentage of the maximum allowed temperature as estimated by the thermal model of the d.c. link components
ModeOpen‑Loop
Minimum0Maximum100
Default Units%
Type8 Bit VolatileUpdate RateBackground write
Display FormatStandardDecimal Places0
CodingRO, ND, NC, PT

Percentage Of d.c. Link Thermal Trip Level (07.035) gives the percentage of the maximum allowed temperature as estimated by the thermal model of the d.c. link components.


Parameter07.036  Percentage Of Drive Thermal Trip Level
Short descriptionDisplays the percentage of the thermal trip level of the temperature monitoring point or thermal model in the drive that is highest
ModeOpen‑Loop
Minimum0Maximum100
Default Units%
Type8 Bit VolatileUpdate RateBackground write
Display FormatStandardDecimal Places0
CodingRO, ND, NC, PT

Percentage Of Drive Thermal Trip Level (07.036)  gives the percentage of the thermal trip level of the temperature monitoring point or thermal model in the drive that is highest. This includes all thermal monitoring points Stack Temperature (07.004), Auxiliary Temperature (07.005), Inverter Temperature (07.034) and Percentage Of d.c. Link Thermal Trip Level (07.035).

Percentage Of d.c. Link Thermal Trip Level (07.035) is used directly to give Percentage Of Drive Thermal Trip Level (07.036), but for all other monitored values which are temperatures this is given by

Percentage of thermal trip level = (Measured Temperature - 40°C) / (Trip temperature - 40°C) x 100%

The location of the measurement or the thermal model that is related to this temperature is given in Temperature Nearest To Trip Level (07.037). If Percentage Of Drive Thermal Trip Level (07.036) exceeds 90% Drive Over-temperature Alarm (10.018) is set to one. If Percentage Of Drive Thermal Trip Level (07.036) reaches 100% one of the trips given in the table below is initiated. The trip can be reset when the percentage of thermal trip level falls below 95%.

Temperature Trip
Inverter Temperature (07.034) OHt Inverter
 Stack Temperature (07.004)  andAuxiliary Temperature (07.005) OHt Power
Percentage Of d.c. Link Thermal Trip Level (07.035) OHt dc bus


Parameter07.037  Temperature Nearest To Trip Level
Short descriptionDisplays the location or the model that corresponds to the value shown in Percentage Of Drive Thermal Trip Level
ModeOpen‑Loop
Minimum0Maximum29999
Default Units 
Type32 Bit VolatileUpdate RateBackground write
Display FormatStandardDecimal Places0
CodingRO, ND, NC, PT

Temperature Nearest To Trip Level (07.037)  shows the location or the model that corresponds to the value shown in Percentage Of Drive Thermal Trip Level (07.036) in the form xxyzz as shown in the table below.

Source xx y zz
Control system 00 1 00: Inverter thermal model ( Inverter Temperature (07.034) )
Control system 00 2 00: D.c. link thermal model ( Percentage Of d.c. Link Thermal Trip Level (07.035) )
Power system 01 0 zz: Thermistor location defined by zz in the power system ( Stack Temperature (07.004) or Auxiliary Temperature (07.005) )
Power system (Large frame only) 01 1 zz: Thermistor location defined by zz in the rectifier


Parameter07.046  Thermistor Type
Short descriptionDefines the thermistor type when used
ModeOpen‑Loop
Minimum0Maximum4
Default0Units 
Type8 Bit User SaveUpdate RateBackground write
Display FormatStandardDecimal Places0
CodingRW, TE

ValueText
0D44081
184
2PT1000
3PT2000
4Other

Thermistor Type (07.046) defines the operation of the temperature feedback interface for DI/O 05 when Digital input 5 mode (08.035) is 1, 2 or 3.

If Thermistor Type (07.046) = 0, the thermistor DIN44081 is designed to react like a temperature switch and therefore Thermistor Temperature (07.050) always reads 0.0°C.

If Thermistor Type (07.046) = 1 to 3 is selected, the digital input operation of the terminal is disabled.

If Thermistor Type (07.046) = 4, any thermistor can be used but Thermistor Temperature (07.050) always reads 0.0°C.


Parameter07.047  Thermistor Feedback
Short descriptionDisplays the measured resistance of the thermistor when used
ModeOpen‑Loop
Minimum0Maximum4000
Default Units
Type16 Bit VolatileUpdate RateBackground write
Display FormatStandardDecimal Places0
CodingRO, FI, ND, NC, PT

Thermistor Feedback (07.047) shows the measured resistance. If Digital input 5 mode (08.035) is 2 then {Th} trip is initiated if the feedback value is higher than Thermistor Trip Threshold (07.048). The trip cannot be reset unless the feedback is below Thermistor Reset Threshold (07.049). The default values for Thermistor Trip Threshold (07.048) and Thermistor Reset Threshold (07.049) are the levels specified in the DIN 44082 standard.


Parameter07.048  Thermistor Trip Threshold
Short descriptionDefines the thermistor trip threshold when used
ModeOpen‑Loop
Minimum0Maximum4000
Default3300Units
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places0
CodingRW

See Thermistor Feedback (07.047).


Parameter07.049  Thermistor Reset Threshold
Short descriptionDefines the thermistor reset threshold when used
ModeOpen‑Loop
Minimum0Maximum4000
Default1800Units
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places0
CodingRW

See Thermistor Feedback (07.047).


Parameter07.050  Thermistor Temperature
Short descriptionDisplays the temperature of the device based on the resistance to temperature characteristic for the specified device
ModeOpen‑Loop
Minimum-50Maximum300
Default Units°C
Type16 Bit VolatileUpdate RateBackground write
Display FormatStandardDecimal Places0
CodingRO, FI, ND, NC, PT

If a KTY84, PT1000 or PT2000 type device is selected for temperature feedback (i.e. Thermistor Type (07.046) = 1 to 3) then Thermistor Temperature (07.050) shows the temperature of the device based on the resistance to temperature characteristic specified for this device. Otherwise Thermistor Temperature (07.050) = 0.0.


Parameter07.051  Analog Input 1 Control
Short descriptionDefines the functionality of analog input 1
ModeOpen‑Loop
Minimum0Maximum5
Default0Units 
Type8 Bit User SaveUpdate RateDrive reset read
Display FormatStandardDecimal Places0
CodingRW

Value Description Analog Input 1 Destination B  (07.090)
0 User defined by Analog Input 1 Destination A (07.010) 00.000
1 Frequency reference 1 01.036
2 Frequency reference 2 01.037
3 Maximum reference clamp 01.006
4 Current limit 04.007
5 Torque reference 04.008

This offers a simple control of parameter Analog Input 1 Destination B  (07.090) to change the analog input 1 functionality.

If Analog Input 1 Control (07.051) is more than 0 then the destination is defined by Analog Input 1 Destination B  (07.090). The destination Analog Input 1 Destination B  (07.090) is written by Analog Input 1 Control (07.051) selection. (i.e. If Analog Input 1 Control (07.051) = 3 then Analog Input 1 Destination B  (07.090) = 01.006)

If Analog Input 1 Control (07.051) is 0 then then the destination is defined by Analog Input 1 Destination A (07.010).


Parameter07.052  Analog Input 2 Control
Short descriptionDefines the functionality of analog input 2
ModeOpen‑Loop
Minimum0Maximum5
Default0Units 
Type8 Bit User SaveUpdate RateDrive reset read
Display FormatStandardDecimal Places0
CodingRW

Value Description Analog Input 2 Destination B  (07.094)
0 User defined by Analog Input 2 Destination A (07.014) 00.000
1 Frequency reference 1 01.036
2 Frequency reference 2 01.037
3 Maximum reference clamp 01.006
4 Current limit 04.007
5 Torque reference 04.008

This offers a simple control of parameter Analog Input 2 Destination B  (07.094) to change the analog input 2 functionality.

If Analog Input 2 Control (07.052) is more than 0 then the destination is defined by Analog Input 2 Destination B  (07.094). The destination Analog Input 2 Destination B  (07.094) is written by Analog Input 2 Control (07.052) selection. (i.e. If Analog Input 2 Control (07.052)= 3 then Analog Input 2 Destination B  (07.094) = 01.006)

If Analog Input 2 Control (07.052) is 0 then then the destination is defined by Analog Input 2 Destination A (07.014).


Parameter07.055  Analog Output 1 Control
Short descriptionDefines the functionality of analog output 1
ModeOpen‑Loop
Minimum0Maximum15
Default0Units 
Type8 Bit User SaveUpdate RateDrive reset read
Display FormatStandardDecimal Places0
CodingRW, BU

Value Description Analog Output 1 Source B (07.099)
0 User defined by Analog Output 1 Source A (07.019) 00.000
1 Post Ramp frequency reference (0 - ±VM_SPEED_FREQ_REF) 02.001
2 Pre Ramp frequency reference (0 - ±VM_SPEED_FREQ_REF) 01.003
3 Motor speed (0 - ±33,000) 05.004
4 Current output (0 - Full Scale Current Kc (11.061)) 04.001
5 Reserved Reserved
6 Percentage load (0 - ± User Current Maximum Scaling (04.024)) 04.020
7 Torque producing current (0 - Full Scale Current Kc (11.061)) 04.002
8 Voltage output (0 - VM_AC_VOLTAGE) 05.002
9 DC bus voltage (0 - VM_DC_VOLTAGE) 05.005
10 Analogue Input 1 (0 - ±100%) 07.001
11 Analogue Input 2 (0 - ±100%) 07.002
12 Power output (0 - ±VM_POWER) 05.003
13 Current limit (0 - ±VM_TORQUE_CURRENT) 04.018
14 Torque reference (0 - ±User Current Maximum Scaling (04.024)) 04.008
15 Reserved Reserved

This offers a simple control of parameter Analog Output 1 Source B (07.099) to change the analog output 1 source.

If Analog Output 1 Control (07.055) is more than 0 then the source is defined by Analog Output 1 Source B (07.099). The source Analog Output 1 Source B (07.099) is written by Analog Output 1 Control (07.055) selection. (i.e. If Analog Output 1 Control (07.055) = 13 then Analog Output 1 Source B (07.099) = 04.018)

If 07.055 is 0 then then the source is defined by Analog Output 1 Source A (07.019) .


Parameter07.061  Analog Input 1 Minimum Reference
Short descriptionDefines the minimum reference for analog input 1
ModeOpen‑Loop
Minimum0.00Maximum100.00
Default0.00Units%
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places2
CodingRW

Analog Input 1 (07.001) can be scaled and limited using the following parameters:

Parameters above can be selected to limit the range of Analog Input 1 (07.001) and also scale it between the minimum and maximum reference.

If Analog Input 1 Minimum Reference (07.061) ≥ Analog Input 1 Maximum Reference (07.063) then Ai1 = 0.00%whatever the input level.

Input Level is limited between Analog Input 1 At Minimum Reference (07.062) and Analog Input 1 At Maximum Reference (07.064)

Analog Input 1 (07.001) = [(Analog Input 1 At Maximum Reference (07.064) - Analog Input 1 At Minimum Reference (07.062)) / (Analog Input 1 Maximum Reference (07.063) - Analog Input 1 Minimum Reference (07.061))] x (Input level - Analog Input 1 Minimum Reference (07.061)) + Analog Input 1 At Minimum Reference (07.062).


Parameter07.062  Analog Input 1 At Minimum Reference
Short descriptionDefines the value of analog input 1 at minimum reference
ModeOpen‑Loop
Minimum-100.00Maximum100.00
Default0.00Units%
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places2
CodingRW

See Analog Input 1 Minimum Reference (07.061).


Parameter07.063  Analog Input 1 Maximum Reference
Short descriptionDefines the maximum reference for analog input 1
ModeOpen‑Loop
Minimum0.00Maximum100.00
Default100.00Units%
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places2
CodingRW

See Analog Input 1 Minimum Reference (07.061).


Parameter07.064  Analog Input 1 At Maximum Reference
Short descriptionDefines the value of analog input 1 at maximum reference
ModeOpen‑Loop
Minimum-100.00Maximum100.00
Default100.00Units%
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places2
CodingRW

See Analog Input 1 Minimum Reference (07.061).


Parameter07.065  Analog Input 2 Minimum Reference
Short descriptionDefines the minimum reference for analog input 2
ModeOpen‑Loop
Minimum0.00Maximum100.00
Default0.00Units%
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places2
CodingRW

See graph in Analog Input 1 Minimum Reference (07.061).

Analog Input 2 (07.002) can be scaled and limited using the following parameters:

Parameters above can be selected to limit the range of Analog Input 2 (07.002) and also scale it between the minimum and maximum reference.

If Analog Input 2 Minimum Reference (07.065) ≥ Analog Input 2 Maximum Reference (07.067) then Ai2 = 0.00% whatever the input level.

Input Level is limited between Analog Input 2 At Minimum Reference (07.066) and Analog Input 2 At Maximum Reference (07.068)

Analog Input 2 (07.002) = [(Analog Input 2 At Maximum Reference (07.068) - Analog Input 2 At Minimum Reference (07.066))/(Analog Input 2 Maximum Reference (07.067) - Analog Input 2 Minimum Reference (07.065))] x (Input level - Analog Input 2 Minimum Reference (07.065))+ Analog Input 2 At Minimum Reference (07.066).


Parameter07.066  Analog Input 2 At Minimum Reference
Short descriptionDefines the value of analog input 2 at minimum reference
ModeOpen‑Loop
Minimum-100.00Maximum100.00
Default0.00Units%
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places2
CodingRW

See Analog Input 2 Minimum Reference (07.065).


Parameter07.067  Analog Input 2 Maximum Reference
Short descriptionDefines the maximum reference for analog input 2
ModeOpen‑Loop
Minimum0.00Maximum100.00
Default100.00Units%
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places2
CodingRW

See Analog Input 2 Minimum Reference (07.065).


Parameter07.068  Analog Input 2 At Maximum Reference
Short descriptionDefines the value of analog input 2 at maximum reference
ModeOpen‑Loop
Minimum-100.00Maximum100.00
Default100.00Units%
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places2
CodingRW

See Analog Input 2 Minimum Reference (07.065).


Parameter07.090  Analog Input 1 Destination B
Short descriptionDefines the secondary destination for analog input 1
ModeOpen‑Loop
Minimum0.000Maximum30.999
Default Units 
Type16 Bit User SaveUpdate RateDrive reset read
Display FormatStandardDecimal Places3
CodingRO, DE, ND, NC, PT

See Analog Input 1 Destination A (07.010).


Parameter07.094  Analog Input 2 Destination B
Short descriptionDefines the secondary destination for analog input 2
ModeOpen‑Loop
Minimum0.000Maximum30.999
Default Units 
Type16 Bit User SaveUpdate RateDrive reset read
Display FormatStandardDecimal Places3
CodingRO, DE, ND, NC, PT

See Analog Input 2 Destination A (07.014).


Parameter07.099  Analog Output 1 Source B
Short descriptionDefines the secondary source for analog output 1
ModeOpen‑Loop
Minimum0.000Maximum30.999
Default Units 
Type16 Bit User SaveUpdate RateDrive reset read
Display FormatStandardDecimal Places3
CodingRO, ND, NC, PT

See Analog Output 1 Source A (07.019).