Features and application

Free standing switchgears RTL

LV transformer switchgear – RTL designed to power LV devices.

It has a wide range of applications in professional transformer stations, industrial sites, shopping centres and other facilities.

 

The switchgear is a free-standing unit with frame structure, made of cold rolled galvanised steel profiles. It has fixed top and side covers and a removable front cover or doors made of RAL 7035 powder-coated sheet steel. On the bottom, it has a perforated cable bracket and foundation fixtures used to mount the switchgear to the floor.

Specification

Each commercially available apparatus can be used as a switching device.

 

Parameter

Value

Rated switching voltage [ Un ]

V

230 / 400

Rated insulation voltage [ Ui ]

V

690

Rated withstand impulse voltage to earth and between phases

kV

8 (1,2/50 μs)

Rated continuous current of main buses [ In ]

A

2000

Rated short-time withstand current (1 s) [ Iew ]

kA

50

Rated peak withstand current [ Ipk ]

kA

105

Front side protection degree

up to IP 40

Mechanical impact resistance

IK 40

 
Current circuits, in the form of busbars, are made of copper or aluminium. As standard, switchgears are designed to be supplied from TN-C network.  Upon request, they can be adapted for TN-S network. Outgoing lines can be made in TN-C, TN-S or TN-C-S system. After consultation, switchgears can be equipped with devices specified by the client, or delivered with different dimensions.

Options

The supplied switchgear can be equipped with a main apparatus to switch the switchgear off under full load.

The main apparatus can be:

  • linear switch disconnector
  • rotary switch disconnector
  • compact circuit breaker
  • air circuit breaker


On the outgoing lines, RTL can have:

  • linear switch disconnectors, e.g. ARS
  • linear fuse blocks
  • other after prior consultation with the manufacturer


Outgoing apparatus is mounted directly on copper busbars. Areas designed for the installation of additional linear apparatus are covered with protective shields.

In addition, the switchgear can be equipped with:

  • current and voltage measuring devices
  • semi-direct energy measurement system, are lighting element
  • capacitor to compensate transformer idling
  • surge protection