Features and application

RTE is a hanging LV transformer switchgear designed to power LV devices. It can be used in urban transformer stations adapted for use only by authorised persons.

 


RTE-rack switchgears

Rack switchgears RTE

Specification

Parameter

Value

Rated switching voltage [ Un ]

V

230 / 400

Rated insulation voltage [ Ui ]

V

690

Rated continuous current of main buses [ In ]

A

1250

Rated short-time withstand current (1 s) [ Iew ]

kA

16

Rated peak withstand current [ Ipk ]

kA

37

Front side protection degree

IP 0X

Mechanical impact resistance

IK 40

Options

Possible operation in TN-S, TN-C, TN-C-S, TT, IT network systems.
The switchgear can be powered directly or through the main disconnector.

The main apparatus can be:

  • linear switch disconnector
  • rotary switch disconnector
  • fuse disconnector
  • or other apparatus after prior consultation with the manufacturer


On outgoing lines, RTE can be equipped with:

  • linear switch disconnectors
  • linear fuse blocks
  • other after prior consultation with the construction department


In addition, the switchgear can be equipped with:

  • area lighting element
  • capacitor to compensate transformer idling
  • surge protection

Contact

Sales

Technical

This site uses cookies. By using this website you agree to the use of cookies in accordance with current browser settings. Using our website without changing the settings for cookies is that they will be stored in memory. More information can be found in our Privacy Policy.
You can change the settings for cookies.

zamknięcie cookie's